1MRK506375-UEN Rev. N
PhSelW1=L1
PhSelW2=L1
InvW2Curr=No
Then the internal calculations will be:
 
I
%
Diff
1
 
I
%
Bias
1
IECEQUATION203 V2 EN-US
The phase selection settings for the second instance of the T1PPDIF function shall be:
PhSelW1=L2
PhSelW2=L1
InvW2Curr=Yes
Then the internal calculations will be:
 
I
%
Diff
2
 
I
%
Bias
2
IECEQUATION204 V2 EN-US
Transformer connection – example 3
132/66kV
U
V
IEC15000172 V2 EN-US
Figure 36:
The HV currents I
side towards the T1PPDIF function. The LV currents I
currents, respectively, for the winding 2 side towards the T1PPDIF function.
To calculate the zero sequence current reduction for U and V phases, see connection example 1.
The phase selection settings for the first instance of the T1PPDIF function shall be:
PhSelW1=(L1-L2)/2
Railway application RER670
Application manual
100
100
IDLW1 IDLW2
I
V
I
I
BaseW
1
BaseW
Max IDLW
1 ,
IDLW
2
Max
I
100
IDLW1 IDLW2
I
U
I
I
BaseW
1
Max IDLW
1 ,
IDLW
2
Max
I
I
U
132kV
I
v
Transformer connection – example 3
and I
shall be connected as IL1 and IL2 currents, respectively, for the winding 1
V
U
© 2017 - 2023 Hitachi Energy. All rights reserved
I
S
2
100
100
I
,
I
V
S
I
BaseW
1
BaseW
2
100
I
S
BaseW
2
100
100
I
,
I
U
S
I
BaseW
1
BaseW
2
and I
S
GUID-945C3857-BE28-484D-B68F-7C9C3BB05441 v2
I
R
66kV
I
S
S
IEC15000172-2-en.vsdx
shall be connected as IL1 and IL2
R
Section 6
Differential protection
(Equation 10)
(Equation 11)
R
81