Hitachi Relion 670 Series Applications Manual page 406

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 21
Basic IED functions
ProductVer
IEDMainFunType
SerialNo
OrderingNo
ProductionDate
21.3
Measured values expander block RANGE_XP
21.3.1
Identification
Function description
Measured values expander block
21.3.2
Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU and VNMMXU),
current and voltage sequence measurement functions (CMSQI and VMSQI) and IEC 61850 generic
communication I/O functions (MVGAPC) are provided with measurement supervision functionality. All
measured values can be supervised with four settable limits, that is low-low limit, low limit, high limit
and high-high limit. The measure value expander block ( RANGE_XP) has been introduced to be
able to translate the integer output signal from the measuring functions to 5 binary signals, that is
below low-low limit, below low limit, normal, above high-high limit or above high limit. The output
signals can be used as conditions in the configurable logic.
21.3.3
Setting guidelines
There are no settable parameters for the measured values expander block function.
400
Describes the firmware version.
The firmware version can be checked from Main menu/Diagnostics/IED status/Product
identifiers
Firmware version numbers run independently from the release production numbers. For
every release number there can be one or more firmware versions depending on the small
issues corrected in between releases.
Describes the product version. Example: 2.1.0
1 is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new hardware added to
the product
3 is the Major revision of the manufactured product this means, functions or hardware is either changed
or enhanced in the product
Main function type code according to IEC 60870-5-103. Example: 128 (meaning line
protection).
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC 61850
IEC 60617
identification
identification
RANGE_XP
-
1MRK506375-UEN Rev. N
SEMOD52451-1 v3
SEMOD113212-2 v4
ANSI/IEEE C37.2
device number
-
SEMOD52434-4 v6
SEMOD113223-4 v2