Hitachi Relion 670 Series Applications Manual page 383

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK506375-UEN Rev. N
18.4.2.1
Identification
Function description
Multiple command and receive
Multiple command and send
18.4.2.2
Application
The IED provides two function blocks enabling several IEDs to send and receive signals via the
interbay bus. The sending function block, MULTICMDSND, takes 16 binary inputs. LON enables
these to be transmitted to the equivalent receiving function block, MULTICMDRCV, which has 16
binary outputs.
18.4.2.3
Setting guidelines
Settings
The parameters for the multiple command function are set via PCM600.
The Mode setting sets the outputs to either a Steady or Pulsed mode.
18.5
SPA communication protocol
18.5.1
Application
SPA communication protocol is an alternative to IEC 60870-5-103, and they use the same rear
communication port.
When communicating with a PC connected to the utility substation LAN via WAN and the utility office
LAN (see Figure 193), and when using the rear optical Ethernet port, the only hardware required for
a station monitoring system is:
Optical fibers from the IED to the utility substation LAN
PC connected to the utility office LAN
Remote
monitoring
IEC05000715 V4 EN-US
Figure 193:
Railway application RER670
Application manual
IEC 61850
identification
MULTICMDRCV
MULTICMDSND
Utility LAN
SPA communication structure for a remote monitoring system via a substation
LAN, WAN and utility LAN
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC 60617
identification
-
-
WAN
IED
IED
Section 18
Station communication
GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v3
ANSI/IEEE C37.2
device number
-
-
SEMOD119915-1 v1
SEMOD115767-5 v7
Substation LAN
IED
IEC05000715-4-en.vsd
M14790-3 v5
M14789-4 v3
IP14614-1 v1
IP14785-1 v1
377