Section 14
Logic
OnDelay: Used to prevent output signals to be given for spurious inputs. Normally set to 0 or a low
value.
OffDelay: Defines a delay of the reset of the outputs after the activation conditions no longer are
fulfilled. It is only used in Steady mode. When used for direct tripping of circuit breaker(s) the off
delay time shall be set to at least 0.150 seconds in order to obtain a satisfactory minimum duration of
the trip pulse to the circuit breaker trip coils.
ModeOutputx: Defines if output signal OUTPUTx (where x=1-3) is Steady or Pulsed.
14.3
Logic for group alarm ALMCALH
14.3.1
Identification
Function description
Logic for group alarm
14.3.2
Application
Group alarm logic function ALMCALH is used to route alarm signals to different LEDs and/or output
contacts on the IED.
ALMCALH output signal and the physical outputs allows the user to adapt the alarm signal to
physical tripping outputs according to the specific application needs.
14.3.3
Setting guidelines
Operation: On or Off
14.4
Logic for group alarm WRNCALH
14.4.1
Identification
Function description
Logic for group warning
14.4.1.1
Application
Group warning logic function WRNCALH is used to route warning signals to LEDs and/or output
contacts on the IED.
WRNCALH output signal WARNING and the physical outputs allows the user to adapt the warning
signal to physical tripping outputs according to the specific application needs.
14.4.1.2
Setting guidelines
Operation On or Off
298
IEC 61850
identification
ALMCALH
IEC 61850
identification
WRNCALH
© 2017 - 2023 Hitachi Energy. All rights reserved
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-70B268A9-B248-422D-9896-89FECFF80B75 v1
GUID-0BDD898A-360B-4443-A5CF-7619C80A17F4 v2
GUID-3EBD3D5B-F506-4557-88D7-DFC0BD21C690 v4
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-FC0DBB7B-FF86-44BF-83D6-DDF120A176DE v1
GUID-B08F2636-33DA-4937-92EB-1A8AC0909AB4 v2
Railway application RER670
1MRK506375-UEN Rev. N
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents