Section 20
Security
20.3.1
Application
Change lock function CHNGLCK is used to block further changes to the IED configuration once the
commissioning is complete. The purpose is to make it impossible to perform inadvertent IED
configuration and setting changes.
However, when activated, CHNGLCK will still allow the following actions that does not involve
reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group
The binary input controlling the function is defined in ACT or SMT. The CHNGLCK function is
configured using ACT.
LOCK
Change lock functionality can be temporarily disabled/overridden using Maintenance menu.
Maintenance menu/Recovery Menu (Password Protected)/Turn off Change-lock (Temporary).
Turning off the change-lock will override the change lock function until the next reboot of the IED. In
this case, the change lock function cannot be activated, and the Override output will indicate that the
change-lock is overridden.
20.4
Denial of service SCHLCCH/RCHLCCH
20.4.1
Application
The denial of service functionality is designed to limit the CPU load that can be produced by Ethernet
network traffic on the IED. The communication facilities must not be allowed to compromise the
primary functionality of the device. All inbound network traffic will be quota controlled so that too
heavy network loads can be controlled. Heavy network load might for instance be the result of
malfunctioning equipment connected to the network.
396
Binary input signal that will activate/deactivate the function, defined in ACT or SMT.
When CHNGLCK has a logical one on its input, then all attempts to modify the IED
configuration and setting will be denied and the message "Error: Changes blocked" will
be displayed on the local HMI; in PCM600 the message will be "Operation denied by
active ChangeLock". The CHNGLCK function should be configured so that it is controlled
by a signal from a binary input card. This guarantees that by setting that signal to a
logical zero, CHNGLCK is deactivated. If any logic is included in the signal path to the
CHNGLCK input, that logic must be designed so that it cannot permanently issue a
logical one to the CHNGLCK input. If such a situation would occur in spite of these
precautions, then please contact the local Hitachi Energy representative for remedial
action.
© 2017 - 2023 Hitachi Energy. All rights reserved
1MRK506375-UEN Rev. N
GUID-51EEC9C7-8ECF-4546-BC26-326861654340 v5
GUID-8C333BC0-AA7A-4ED1-A772-18C22E8EEE62 v8
GUID-64F4D905-9F73-4073-B8F6-8D373155316A v5
Railway application RER670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents