Hitachi Relion 670 Series Applications Manual page 314

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Logic
14.14
Comparator for real inputs - REALCOMP
14.14.1
Function revision history
Document
revision
A
B
C
D
E
F
G
H
M
N
14.14.2
Identification
Function description
Comparator for real inputs
14.14.3
Application
The function gives the possibility to monitor the level of real values in the system relative to each
other or to a fixed value. It is a basic arithmetic function that can be used for monitoring, supervision,
interlocking and other logics.
14.14.4
Setting guidelines
Setting procedure on the IED:
EnaAbs: To select the comparison type between signed and absolute values.
Absolute: Comparison is performed with absolute values of input and reference.
Signed: Comparison is performed with signed values of input and reference.
RefSource: To select the reference source between input and setting for comparison.
Input REF: The function will take reference value from input REF
Set Value: The function will take reference value from setting SetValue
SetValue: To set the reference value for comparison when setting RefSource is selected as Set
Value. If this setting value is less than 0.2% of the set unit then the output INLOW will never pickup.
RefPrefix: To set the unit of the reference value for comparison when setting RefSource is selected
as SetValue. It has 5 unit selections and they are Milli, Unity, Kilo, Mega and Giga.
308
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
Settings EqualBandLow and EqualBandHigh maximum value has been changed to 50.00
in order to make the function more user friendly.
2.2.3
-
2.2.4
-
2.2.4
-
2.2.5
-
2.2.6
-
2.2
-
IEC 61850
identification
REALCOMP
© 2017 - 2023 Hitachi Energy. All rights reserved
GUID-D91005E2-2607-4FE2-A500-29D1F15CAEC4 v3
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
IEC 60617
ANSI/IEEE C37.2
identification
device number
Real<=>
GUID-5F7B1683-9799-4D27-B333-B184F8861A5B v1
GUID-DE69FF5B-7D34-4A30-9060-214E98BFF798 v3
Railway application RER670