Phase to earth fault
IEC16000126 V1 EN-US
Figure 64:
The residual fault current can be written:
2
I
0
2
IECEQUATION16034 V1 EN-US
Where
U
is the phase voltage in the fault point before the fault
phase
Z
is the total positive sequence impedance to the fault point. Z
1
Z
is the total zero sequence impedance to the fault point. Z
0
R
is the fault resistance.
f
The residual voltages in stations A and B can be written:
U
2
0
A
IECEQUATION16097 V1 EN-US
U
2
0
B
IECEQUATION16098 V1 EN-US
The residual power, measured by the sensitive earth fault protections in A and B will be:
S
2
0
A
IECEQUATION16099 V1 EN-US
Railway application RER670
Application manual
Source impedance
Z
(pos. seq)
sc
Z
(pos. seq)
T,1
R
Z
(zero seq)
T,0
U
0A
2I
0
Z
lineAB,1
Z
lineAB,0
U
0B
Z
lineBC,1
Z
lineBC,0
IEC16000126-1-en.vsdx
Equivalent of power system for calculation of setting
2
U
phase
 
Z
Z
2
R
1
0
f
I
Z
2
R
0
T
,0
N
I
Z
2
R
Z
0
T
,0
N
lineAB
U
2
I
0
A
0
© 2017 - 2023 Hitachi Energy. All rights reserved
N
Substation A
(pos. seq)
(zero seq)
Substation B
(pos. seq)
(zero seq)
= Z
0
,0
= Z
+Z
+Z
+Z
1
sc
T,1
lineAB,1
lineBC,1
+2R
+Z
+Z
T,0
N
lineAB,0
lineBC,0
Section 8
Current protection
(Equation 48)
(Equation 49)
(Equation 50)
(Equation 51)
161