1MRK506375-UEN Rev. N
BU-TRIP
ZCVPSOF-TRIP
IEC05000315-WMF V4 EN-US
Figure 78:
BU-TRIP
ZCVPSOF-TRIP
IEC05000316-WMF V4 EN-US
Figure 79:
12.2.3.13
Thermal overload protection holding the auto recloser back
If the THOLHOLD input (thermal overload protection holding auto reclosing back) is activated, it will
keep the auto recloser on a hold until it is reset. There may thus be a considerable delay between
start of the auto recloser and the breaker closing command to the circuit breaker. An external logic
limiting the time and sending an inhibit to the INHIBIT input can be used. The input can also be used
to set the auto recloser on hold for a longer or shorter period.
12.2.4
Setting guidelines
12.2.4.1
Configuration
Use the PCM600 configuration tool to configure signals.
Auto recloser function parameters are set via the local HMI or Parameter Setting Tool (PST).
Parameter Setting Tool is a part of PCM600.
Recommendations for input signals
Please see Figure
Railway application RER670
Application manual
SMBRREC
OR
INHIBIT
UNSUCCL
CCRBRF
TRBU
Lock-out arranged with an external lock-out relay
SMBRREC
OR
INHIBIT
UNSUCCL
Functional key,
CCRBRF
SOFTWARE
OR IO RESET
TRBU
MAN CLOSE
OR
SMBRREC CLOSE
SESRSYN
MANENOK
MANSYOK
Lock-out arranged with internal logic with manual closing going through in IED
80
and default factory configuration for examples.
© 2017 - 2023 Hitachi Energy. All rights reserved
SMBO
OR
SMPPTRC
OR
SETLKOUT
CLLKOUT
RESET LOCK-OUT
RSTLKOUT
AND
OR
Lock-out
RXMD1
11
21
12
CLOSE COMMAND
MAIN ZAK CLOSE
IEC05000315-4-en.vsd
SMBO
CLOSE COMMAND
IEC05 000 316-4-en.vsdx
Section 12
Control
M12391-226 v3
IP14929-1 v1
M12399-3 v3
M12399-7 v10
215

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents