1MRK506375-UEN Rev. N
Disturbance report function can handle a maximum of 3 simultaneous disturbance recordings.
15.6.4.2
Binary input signals
Up to 352 binary signals can be selected among internal logical and binary input signals. The
configuration tool is used to configure the signals.
For each of the 352 signals, it is also possible to select if the signal is to be used as a trigger for the
start of the Disturbance report and if the trigger should be activated on positive (1) or negative (0)
slope.
OperationN: Disturbance report may trig for binary input N (On) or not (Off).
TrigLevelN: Trig on positive (Trig on 1) or negative (Trig on 0) slope for binary input N.
Func103N: Function type number (0-255) for binary input N according to IEC-60870-5-103, that is,
128: Distance protection, 160: overcurrent protection, 176: transformer differential protection and
192: line differential protection.
Info103N: Information number (0-255) for binary input N according to IEC-60870-5-103, that is,
69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
15.6.4.3
Analog input signals
Up to 40 analog signals can be selected among internal analog and analog input signals. PCM600 is
used to configure the signals.
The analog trigger of Disturbance report is not affected if analog input M is to be included in the
disturbance recording or not (OperationM = On/Off).
If OperationM = Off, no waveform (samples) will be recorded and reported in graph. However, Trip
value, pre-fault and fault value will be recorded and reported. The input channel can still be used to
trig the disturbance recorder.
If OperationM = On, waveform (samples) will also be recorded and reported in graph.
NomValueM: Nominal value for input M.
OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance report may trig for high/low
level of analog input M (On) or not (Off).
OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relative nominal value for
analog input M in percent of nominal value.
15.6.4.4
Sub-function parameters
All functions are in operation as long as Disturbance report is in operation.
Indications
IndicationMaN: Indication mask for binary input N. If set (Show), a status change of that particular
input, will be fetched and shown in the disturbance summary on local HMI. If not set (Hide), status
change will not be indicated.
Railway application RER670
Application manual
For retrieving remote data from LDCM module, the Disturbance report function should be
connected to a 8 ms SMAI function block if this is the only intended use for the remote
data.