Set the value of "Device Area Capacity" in "Device Area" in "CPU Parameter" to 80K word and the value of "File Storage
Area Capacity" to 88K word.
[CPU Parameter]  [Memory/Device Setting]  [Device/Label Memory Area Setting]  [Device/Label Memory Area
Capacity Setting]
5.
Set the values of "Points" of "Internal Relay M", "Link Relay B", "Data Register D", and "Link Register W" to 32K in the
[Detailed Setting] window in "Device Setting".
[Memory/Device Setting]  [Device/Label Memory Area Setting]  [Device/Label Memory Area Detailed Setting]
For the R04CPU, if the number of points for the device assignment is greater, the capacity of the device/
memory area may be insufficient. In that case, replace the module with a CPU module having larger capacity
or insert an extended SRAM cassette.