Connectable Devices (For Unicast Mode) - Mitsubishi Electric MELSEC iQ-R Series User Manual

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Connectable devices (for unicast mode)

This section describes the connectable devices when "Communication Mode" under "Application Settings" is set to "Unicast".
When the communication speed for the master station is set to 1Gbps
This mode indicates the availability of connection with a network configuration device when "Communication Speed" of the
master station is set to "1Gbps".
: Connection available, : Connection available via a switching hub, : Connection not available
S: TSN hub available
H: General-purpose hub available
Device on the master station
side
(A device near the master
station)
Master station
1Gbps
(CC-Link IE TSN
Class B device)
Local station
1Gbps
(CC-Link IE TSN
100Mbps
Class B device)
Remote station
1Gbps
(CC-Link IE TSN
100Mbps
Class B device)
*1 For a device station with a communication speed of 100Mbps, set "Communication Period Setting" to "Low-Speed".
*2 A connection cannot be established if the total cyclic data size of all device stations on the 100Mbps device side exceeds 2K bytes. This
includes the devices with a communication speed of 100Mbps that form a boundary between the communication speed of 1Gbps and
100Mbps. ( Page 64 Calculation of the total cyclic data size)
*3 When the firmware version of the master station is "11" or earlier, only one of P1 or P2 can be used. (To use both P1 and P2 of the
master station, set up a multicast mode structure.)
Precautions
When a TSN hub is used, check the TSN hub specifications on the CC-Link Partner Association website (www.cc-link.org).
When the communication speed for the master station is set to 100Mbps
This mode indicates the availability of connection with a network configuration device when "Communication Speed" of the
master station set to "100Mbps".
: Connection available, : Connection available via a switching hub, : Connection not available
S: TSN hub available
H: General-purpose hub available
Device on the master station
side
(A device near the master
station)
Master station
100Mbps
(CC-Link IE TSN
Class B device)
Local station
1Gbps
(CC-Link IE TSN
100Mbps
Class B device)
Remote station
1Gbps
(CC-Link IE TSN
100Mbps
Class B device)
*1 For a device station with a communication speed of 100Mbps, set "Communication Period Setting" to "Basic Period" or "Normal-Speed".
Precautions
When a TSN hub is used, check the TSN hub specifications on the CC-Link Partner Association website (www.cc-link.org).
Device on the end side (A device far from the master station)
Local station (CC-Link IE TSN
Class B device)
1Gbps
100Mbps
S
S
S
Device on the end side (A device far from the master station)
Local station (CC-Link IE TSN
Class B device)
1Gbps
100Mbps
*1
S
*1
S
*1
S
Remote station (CC-Link IE
TSN Class B device)
1Gbps
100Mbps
*1*3
S
S
*1*2*3
S
S
*1*2*3
S
S
*1*2*3
S
Remote station (CC-Link IE
TSN Class B device)
1Gbps
100Mbps
*1
S
*1
S
*1
S
5 SYSTEM CONFIGURATION (RJ71GN11-T2)
5.1 Structure with CC-Link IE TSN Class B Devices Only
Ethernet device
1Gbps
100Mbps
*3
SH
SH
*3
SH
SH
*3
SH
SH
*3
SH
Ethernet device
1Gbps
100Mbps
SH
SH
SH
5
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rj71gn11-t2Rj71gn11-sx

Table of Contents