1.2

RJ71GN11-SX

This section describes the names of each part of the RJ71GN11-SX.
(1)
(2)
(3)
(4)
(5)
No.
Name
(1)
RUN LED
*1
ERR LED
MST LED
*1
D LINK LED
P1
SD/RD LED
*1
L ERR LED
P2
SD/RD LED
*1
L ERR LED
(2)
Dot matrix LED
(3)
P1
(4)
P2
(5)
Production
information marking
*1 The LED is always off in offline mode.
*2 The L ERR LED does not turn on for loopback stations whose station number has not been set.
If a station whose station number has not been set enters the ring structure, the L ERR LED of the loopback station does not turn on.
1 PART NAMES
20
1.2 RJ71GN11-SX
Description
Indicates the operating status.
On: Normal operation
Off: Error ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
Indicates the error status of the module. ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
On: Error detected in all stations
Flashing (500ms interval): Data link faulty station detected
• Unicast mode: Flashing only at the master station
• Multicast mode: Flashing at the master station and local station.
Flashing (200ms interval): Error
Off: Normal operation
Indicates the operating status.
On: Operating as a master station
Off: Operating as a local station
Indicates the cyclic transmission status.
On: Cyclic transmission being performed
Flashing: Cyclic transmission stopped
Off: Disconnected
Indicates the data sending/receiving status.
On: Data being sent or received
Off: Data not sent nor received
Indicates the line error status. ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
On: The following errors are occurring in the line connected to the own station port.
• A receive data is faulty (receive frame error).
• Loopback is performed in the own station.
Off: The module or line is in the following status.
• A received data is normal (receive frame normal)
• Loopback is not performed in the own station.
Same as P1
Displays the station number set for the module.
Station number or parameter not set: "  "
Master station: 0
Local station: 1 to 120
■In module communication test mode
Displays the module communication test result. ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
■In offline mode
Displays "".
Port for CC-Link IE TSN connection. Connect an optical fiber cable. (Page 67 WIRING)
Same as P1
Shows the production information (16 digits) of the module.