Huawei LUNA2000-100KTL-M1 User Manual page 96

Smart power control system
Hide thumbs Also See for LUNA2000-100KTL-M1:
Table of Contents

Advertisement

LUNA2000-100KTL-M1 Smart Power Control System
User Manual
Alarm
Alarm
ID
Name
2040
DC
Component
Overhigh
2051
Abnormal
Residual
Current
2061
Abnormal
Grounding
Issue 02 (2023-01-10)
Severi
Possible Cause
ty
Major
Cause ID = 1
The DC component in the AC
current exceeds the upper
threshold.
Major
Cause ID = 1
The ground insulation
resistance decreases during
device operation.
Major
Cause ID = 1
1. The neutral wire or PE
cable of the device is not
connected.
2. The output mode of the
device does not match the
actual cable connection.
Copyright © Huawei Technologies Co., Ltd.
8 Alarm Reference
Suggestion
1. The device detects its
external working conditions
in real time. After the fault
is rectified, the device
automatically recovers.
2. If the alarm occurs
frequently, contact your
dealer or technical support.
1. If the alarm occurs
occasionally, the external
circuit may be abnormal
temporarily. The device will
automatically recover after
the fault is rectified.
2. If the alarm occurs
frequently or persists, check
whether the DC-to-ground
impedance is too low.
Power off the device (turn off
the AC switch and DC switch,
and wait for a period specified
on the device safety warning
label), and then perform the
following operations:
1. Check that the PE cable of
the device is connected
properly.
2. If the device is connected to
a TN power grid, check
whether the neutral wire is
properly connected and
whether the voltage to
ground is normal.
3. After powering on the
device, check whether the
output mode set on the
device matches the actual
cable connection.
90