LUNA2000-100KTL-M1 Smart Power Control System
User Manual
No.
Category
10
11
12
13
14
15
Q-P
characteristic
curve
16
PF-U curve
17
18
Cosφ-P/Pn
characteristic
curve
19
Issue 02 (2023-01-10)
Parameter
Q-U characteristic
curve mode
Delay for Q-U
characteristic curve
to take effect
Power percentage
for triggering Q-U
scheduling
Power percentage
for exiting Q-U
scheduling
Limit value for
minimum PF of Q-
U characteristic
curve
Q-P characteristic
curve
PF-U characteristic
curve
PF (U) voltage
detection filter
time
Cosφ-P/Pn
characteristic curve
Reactive power
compensation
(cosφ-P) trigger
voltage
Copyright © Huawei Technologies Co., Ltd.
Description
Specifies the reactive power
compensation mode of the
device output.
Specifies the delay time for Q-U
adjustment.
Specifies the reference apparent
power in percent. When the
actual apparent power of the
device is greater than the value
of this parameter, the Q-U
characteristic curve scheduling
function is enabled.
Specifies the P/Pn when the
device exits the Q-U scheduling.
Specifies the minimum power
factor for Q-U adjustment.
The device adjusts Q/Pmax (the
ratio of the reactive power to the
maximum active power) in real
time based on P/Pmax (the ratio
of the active power to the
maximum active power).
The device adjusts the power
factor in real time based on U/
Un(%) (the ratio of the actual
power grid voltage to the rated
power grid voltage).
Specifies the time for filtering
the grid voltage in the PF-U
curve.
The device adjusts the output
power factor cosφ in real time
based on P/Pn (%).
Specifies the voltage threshold
for triggering reactive power
compensation based on the
curve.
6 Power-On Commissioning