Huawei LUNA2000-100KTL-M1 User Manual page 66

Smart power control system
Hide thumbs Also See for LUNA2000-100KTL-M1:
Table of Contents

Advertisement

LUNA2000-100KTL-M1 Smart Power Control System
User Manual
No.
Category
5
6
7
8
9
Soft start time
Issue 02 (2023-01-10)
Parameter
Description
Active power
Specifies the active power
threshold when
threshold as a fixed value.
communication
fails (kW)
Reactive power
Specifies the protection
mode when
threshold of the reactive
communication
power after communication is
fails
interrupted, including Q/S
and power factor.
Reactive power
Specifies the Q/S threshold of
threshold when
the reactive power (%)
communication
fails (%)
Reactive power
Specifies the power factor
threshold when
threshold of the reactive
communication
power (PF)
fails
Soft start time
Specifies the duration
(s)
required for gradual power
increase when the device
starts.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Remarks
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and Active
power threshold
when
communication
fails is set to a fixed
value.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and
Reactive power
threshold when
communication
fails is set to Q/S.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and
Reactive power
threshold when
communication
fails is set to Power
factor.
-