LUNA2000-100KTL-M1 Smart Power Control System
User Manual
exception occurs, select a proper overcurrent protection device in compliance with
local power distribution regulations.
● Do not connect loads between a PCS and an AC switch that directly connects to
● If an AC switch is used with specifications beyond local standards, regulations,
Each PCS must be equipped with an AC output switch. Multiple PCSs cannot
connect to the same AC switch.
● The cable outer diameter can be measured using the ruler sticker in the
● Ensure that the cable jacket is in the maintenance compartment.
● Ensure that the AC power cables are connected securely. Otherwise, the Smart
● Do not pull the cables horizontally after they have been secured, as this may
Step 1 Prepare cables by referring to section
Step 2 Remove rubber rings according to the cable diameter range.
Step 3 Connect the AC power cables to the terminal block and ensure that the cables are
securely connected.
Issue 02 (2023-01-10)
WARNING
the PCS. Otherwise, the switch may trip by mistake.
or the Company's recommendations, the switch may fail to turn off in a timely
manner in case of exceptions, causing serious faults.
CA UTION
NO TICE
maintenance compartment.
PCS may fail to operate, or become overheated during operation due to an
unreliable connection, which will damage the terminal block.
damage the wiring terminals.
Copyright © Huawei Technologies Co., Ltd.
A Crimping an OT or DT
5 Electrical Connections
Terminal.
41