Huawei FusionModule1000A20 Maintenance Manual page 66

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One
Data Center
Maintenance Guide
Symptom
Alarm
None
The
Communicat
indicator on
ion Failed
the external
door of the
ATS PDF is
on, but the
controller
fails to
display
information.
Issue 03 (2022-12-15)
Possible
Cause
A short-
circuit
occurs inside
the ATS PDF.
The power
cables to the
ATS
controller
are loose.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Common Faults and Troubleshooting Measures
Solution
1. Ask the customer to disconnect the power supply,
turn off the cable inlet switch, remove the
protective panel from the PDF, and use a
multimeter to check whether there is voltage in
the PDF.
2. If a short circuit has occurred inside the ATS PDF,
switch on all output MCBs, and use a high-
precision multimeter to check whether every two
of L1, L2, L3, N, and PE are directly connected.
Use an insulation resistance tester or a withstand
voltage tester to check whether the insulation
resistance and leakage current meet the
requirements of the equipment. If not, check the
cable connection.
3. Check whether there are traces of burning black
inside the PDF or whether a short circuit is caused
by a conductor dropping to the copper bar. Check
whether the input and output cables are
connected properly. Rectify any cable connection
fault.
4. After the fault is rectified, use a multimeter to
measure the voltage according to 2. If the voltage
is correct, power on the equipment again.
1. Ask the customer to disconnect the power supply,
turn off the cable inlet switch, remove the
protective panel from the PDF, and use a
multimeter to check whether there is voltage in
the PDF.
2. Open the front panel and check whether the
green Phoenix terminal on the controller is
properly installed and cables are correctly
connected.
3. Use a multimeter to check which input is normal,
and transfer the ATS switch to the normal input
by operating the handle.
4. Ask the customer to disconnect the power supply
for repair. After power-off, reconnect the cables.
59

Advertisement

Table of Contents
loading

Table of Contents