FusionModule1000A20 Prefabricated All-in-One
Data Center
Maintenance Guide
Item
Method
Cables
Check cable
connections.
Check whether
cables are intact.
Issue 03 (2022-12-15)
Check Standard
Cables are
securely
connected
without bare
terminals.
● Cable jackets
are free from
damage or
cracks.
● No cable
overheats
due to
overload and
the loads are
within the
rated
capacity of
the cables
(the cables
works only a
very short
time under
overload
situations).
● The bend
radius of
cables meets
requirements.
● The cable
armor is
intact.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Routine Maintenance
Troubleshooting
Secure terminal connections, and
replace terminals that do not meet
requirements. For details, see the
installation guide for the corresponding
solution.
Replace parts that do not meet
requirements.