3.5.17 Output variation limiter (buffer memory address 44, 76: Un\G44, Un\G76)

3.5.18 Sensor compensation value setting (buffer memory address 45, 77: Un\G45,
Un\G77)
3 - 88
(1) A sudden change in the manipulated value is controlled by setting this value.
Set the variation of the manipulated value per second.
Mainpulated value (MV)
Mainpulated value (MV)2
Mainpulated value (MV)1
(2) The setting range is 0 to 1000 (0.1 to 100.0%).
For example, when the output variation limiter is set to 10 (1.0%), the output
variation will be 1% per second at a sudden manipulated value change of 50%,
and it will take 50 seconds until the output value changes to 50% actually.
(3) The default is set to 0. With the default setting, a sudden change cannot be
controlled.
(1) A sensor compensation value is set. The value is used when there is an error
between the measured value and the actual measured value due to
measurement conditions (refer to Section 3.2.5).
(2) For thermocouple input, the setting range is -5000 to 5000 (-500.0 to 500.0
For micro voltage, voltage, and current input, the setting range is -5000 to 5000
(-50.00 to 50.00 %) for full-scale of the set input range.
Output variation limiter
1 sec.
MELSEC-Q
t
).