Execution Times Monitor (Buffer Memory Address 258, 514: Un\G258, Un\G514); Pattern End Output Flag (Buffer Memory Address 259, 515: Un\G259, Un\G515); End Status Flag (Buffer Memory Address 260, 516: Un\G260, Un\G516); Wait Status Flag (Buffer Memory Address 261, 517: Un\G261, Un\G517) - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.5.55 Execution times monitor (buffer memory address 258, 514: Un\G258, Un\G514)

3.5.56 Pattern end output flag (buffer memory address 259, 515: Un\G259, Un\G515)

3.5.57 End status flag (buffer memory address 260, 516: Un\G260, Un\G516)

3.5.58 Wait status flag (buffer memory address 261, 517: Un\G261, Un\G517)

3.5.59 Hold status flag (buffer memory address 262, 518: Un\G262, Un\G518)

3 - 106
(1) Execution times of the currently executed program pattern are stored.
(2) Execution times are updated at the pattern end.
When the program pattern is linked, execution times are updated at the pattern
end of the final program pattern.
(3) Upper limit of the storage value is 30000. If any value greater than 30000, the
monitor goes back to 0 and starts to count again.
(1) This is a flag to check the pattern end output status at the completion of the
program control of the final segment.
The pattern end output status at the completion of the program control of the
final segment can be checked.
• Pattern end output OFF: 0 is stored.
• During pattern end output: 1 is stored.
(1) This is a flag to notify the completion of the program control.
(2) This flag turns on (or becomes 1) at the completion of the program control.
When 1 (RESET) is set in Program control run/reset (buffer memory address: 57,
89), this flag turns off (or becomes 0).
(1) This is a flag to check the wait status of the program control.
• Cancelling wait status: 0 is stored.
• Wait status: 1 is stored.
(1) This is a flag to check if the program control is in hold status.
(2) This flag will be 1 when the program control is paused (when 1 is set in Hold
command (buffer memory address: 201, 217)).
• Cancel hold status: 0 is stored.
• In hold status: 1 is stored.