3 SPECIFICATIONS
3.5.46 Scaling range upper/lower limit value (buffer memory address 197, 198, 213, 214:
Un\G197, Un\G198, Un\G213, Un\G214)
3.5.47 Scaling width upper/lower limit value
(buffer memory address 199, 200, 215, 216: Un\G199, Un\G200, Un\G215,
Un\G216)
3 - 102
(1) The upper limit value and lower limit value of the scaling range is set.
The setting range is within the input range.
(a) Thermocouple input
Set the scaling range of measured temperature value.
When the upper limit value is set equal to the lower limit value, the scaling
is not performed.
(b) Micro voltage, voltage, current input
Set the digital value corresponding to the upper and lower limit values of
the input range.
However, the full-scale of the setting value is 20000.
(2) The following lists the setting ranges.
• Thermocouple input
• Micro voltage, voltage, current input : -32768 to 32767
(3) The scaling is not performed with the default value 0.
(4) For details of the scaling function, refer to Section 3.2.14.
(1) The upper limit value and lower limit value of the scaling width is set.
(a) Thermocouple input
Set the scaling width of measured temperature value.
(b) Micro voltage, voltage, current input
Not used.
If the setting is made, it is ignored.
(2) The following lists the setting ranges.
• Thermocouple input
• Micro voltage, voltage, current input : - (The setting is ignored.)
(3) The scaling is not performed with the default value 0.
(4) For details of the scaling function, refer to Section 3.2.14.
: within the input range
(However, the full-scale is 20000.)
: -32768 to 32767