Pid Constant Setting; (Buffer Memory Address 35 To 37, 67 To 69: Un\G35 To Un\G37, Un\G67 To Un\G69) - Mitsubishi Electric MELSEC-Q Series User Manual

Loop control module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

3 SPECIFICATIONS

3.5.14 PID constant setting

(buffer memory address 35 to 37, 67 to 69: Un\G35 to Un\G37, Un\G67 to Un\G69)

3 - 85
(1) The proportional band (P), integral time (I), and derivative time (D) for performing
PID operation in normal control mode are set.
(2) For thermocouple input, set the proportional band (P) with temperature. For
micro voltage, voltage and current, set with % for full-scale.
(3) Set the proportional band (P), integral time (I), and derivative time (D) within the
following ranges.
(a) For PI control, set the derivative time to 0.
(b) For P control, set the derivative time and the integral time to 0.
Item
Proportional
band (P) setting
Integral time (I)
Derivative time
(D)
Address
Default
CH1
CH2
35
67
100
36
68
400
37
69
100
MELSEC-Q
Setting range
1 to full scale
Thermocouple
Micro voltage,
voltage, current
(0.1 to 1000.0%)
0 to 32767 (0.0 to 3276.7s)
0 to 32767 (0.0 to 3276.7s)
(×0.1 )
1 to 10000
3 - 85