3 SPECIFICATIONS
3 - 33
(d) PV start 3 (time shortened/find type)
Through the entire program pattern, the Q62HLC searches the point where the
measured value (PV) at the start of program control and the set value (SV) of
each segment match. When a matching point is found, program control starts
from that point. When multiple matching points are found, the first point is
prioritized.
To use PV start 3 (time shortened/find type), Set value at program control start
(SV_PCS) setting (buffer memory address: 501, 757) must be set in advance.
1) When a match point was found
Program control starts from the first matching point, shortening time.
2) When no match point was found
Program control starts from time 0, specifying the set value in Set value at
program control start (SV_PCS) setting (buffer memory address: 501, 757) as
a set value (SV).
POINT
Only the program pattern that is executed first is searched for a match point. Even if
the link setting is configured, the program pattern of the link destination is not
searched for.
MELSEC-Q
3 - 33