SPECIFICATIONS
3.4.8 CH

Digital output value (buffer memory address 11 to 18: Un\G11 to Un\G18)

3 - 29
(1)
Digital output values after A/D conversion are stored in CH
value (buffer memory address 11 to 18: Un\G11 to Un\G18) for each channel.
(2)
Digital output value is expressed with 16-bit signed binary values.
b15 b14 b13b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
For other than the data section and a signed bit, it becomes
1 for a negative (when b15 is 1) and 0 for a positive (when b15 is 0).
Signed bit
1: Negative
0: Positive
(3)
While Operating condition setting request (Y9) is on, 0 is stored to the buffer
memory area.
(4)
When reading Digital output value, use A/D conversion completed flag (XE) or
A/D conversion completed flag (buffer memory address 10: Un\G10) as an
interlock.
Data section
Resolution 1/4000
Resolution 1/12000, 1/16000 14 bits
MELSEC-Q
Digital output
12 bits
3 - 29