Huawei PDU8000 User Manual page 94

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
Procedure
Step 1 Remove the CAN and RS485_1 communications cables connected to the MDU, as shown in
Figure
Step 2 Remove the four screws fixing the MDU and set them aside, as shown in
Figure 9-11 Removing the MDU
Step 3 Hold the MDU front panel by one hand, and push out the MDU from the fastener on the front
panel by the other hand.
Step 4 Align the new MDU with the mounting holes, snap the bottom of the new MDU into the
fastener on the front panel until you hear a slight click sound, and push the top of the MDU in
place.
Step 5 Secure the new MDU to the front panel using the screws you removed.
Step 6 Connect the CAN and RS485_1 communications cable to the MDU.
Step 7 After the MDU is replaced, the new MDU automatically checks whether its configurations are
consistent with the rack configuration during startup. If an inconsistency is found, the MDU
displays a synchronization dialog box, as shown in
1.
2.
Issue 01 (2016-02-27)
The MDU can be replaced online without disconnecting the power supply.
9-11.
When removing cables, label the cables with corresponding terminal ports for later connection.
Click OK to synchronize the configurations. The MDU restarts.
If you click Cancel (not recommended), the configurations will not be synchronized, and
the MDU displays the same dialog box after the next startup.