Alarm
Alarm
Name
Severity
Branch
Critical
overload
Max. br.
Warning
cur. exceed
Min. br.
Warning
cur. exceed
Main input
Major
br. current
shock
Three
Warning
phase
current
imb.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Impact
Cause
The current of
The branch is
a branch
overloaded.
exceeds 1
times of the
rated current
(multiple:
1–1.2;
confirmation
time: 1–10s).
The current of
The branch is
a branch
overloaded.
exceeds 0.8
time of the
rated current
(multiple:
0.8–1).
The current of
N/A
a branch
exceeds 0.6
time of the
rated current
(multiple:
0.6–0.8;
confirmation
time: 1–10s).
A surge
The
current three
insulation of
times greater
a branch is
than the rated
abnormal.
current is
detected in a
branch
(multiple:
1.5–5).
The difference
The loads of
between
phases L1,
currents on
L2, and L3
phases L1, L2,
are
and L3 of the
imbalanced.
input power or
an output
branch
exceeds 15%
(Configurable
range:
5–50%).
9 Operation and Maintenance
Solutions
Check the load
power of the branch.
Check the load
power of the branch.
N/A
Check the cable
insulation of the
output branch.
Check all output
loads and adjust
loads of phases L1,
L2, and L3.