Huawei PDU8000 User Manual page 81

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
No.
8
9
10
11
12
Issue 01 (2016-02-27)
Alarm
Alarm
Name
Severity
Main input
Critical
open phase
Main input
Critical
outage
Main input
Major
CT reverse
connect
Main input
Critical
breaker
tripping
Main input
Critical
overvoltag
e
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Impact
Cause
A phase of the
The input
input power
power is
has no voltage
abnormal.
or has a
voltage lower
than the
threshold
(0–60 V).
The input
The input
power has
power is
three open
abnormal.
phases.
The common
N/A
polarity
terminal and
common
terminal on a
phase current
transformer of
a mains phase
are reversely
connected.
The mains
The back-end
switch has
is
tripped.
short-circuite
d or
experiences
overcurrent.
Input
The input
overvoltage:
power is
Input voltage
abnormal.
V > 1.2 x
Rated voltage
(Multiple:
1.05–1.25;
confirmation
time: 2–10s).
9 Operation and Maintenance
Solutions
Check the input
power.
Check the input
power.
Switch cables
connected to the
common polarity
terminal and
common terminal.
Figure 9-1
uses
dual-input as an
example to show the
cable connection for
the common polarity
terminal and
common terminal of
the current
transformer for route
I phase L1.
Check whether the
back-end current is
short-circuited or
experiences
overcurrent.
Check the input
power.
75