Huawei PDU8000 User Manual page 78

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
Powering off the PDC may interrupt all services. Before disconnecting power, ensure that
related emergency plans have been worked out and permissions have obtained from parties
involved. Huawei bears no responsibility for any accidents or loss.
Table 9-2 Routine maintenance for the PDC
Maintenance
Item
Three phase
power
indicators
Surge
protection
module
Liquid crystal
display (LCD)
screen on the
PDC
Connections of
input power
cables and
output power
cables
Signs of rodent
movements in
the PDC
Issue 01 (2016-02-27)
Mainten
Operation
ance
Guide
Interval
Check the
Monthly
luminance of
the indicators.
Monthly
Check the
status of the
surge
protection
module
indicator and
circuit breaker.
Monthly
Touch the
LCD screen
with your
finger.
Visual
Monthly
observation
Visual
Monthly
observation
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 Operation and Maintenance
Expected
Exception Handling
Result
The three
Replace the indicator
phase power
that generates no or
indicators are
dim light.
steady on.
The surge
If the surge
protection
protection module
module
indicator is red,
indicator is
replace the surge
green.
protection module.
The circuit
If the circuit breaker
breaker is
is switched off,
switched
switch it on.
on.
The LCD
Check whether the
screen panel
power cable is properly
does not
connected, and replace
display
the LCD screen if
information
necessary.
properly.
The cables
Take measures
are not
depending on the
damaged.
severity.
The
terminals
are intact
and secure
and free
from spark
signs and
rust.
If there is a sign of
N/A
rodent movements, ask
a professional for
advice.
72

Advertisement

Table of Contents
loading