Huawei PDU8000 User Manual page 46

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
Table 5-3 Cable installation checklist
No.
1
2
3
4
5
6
Issue 01 (2016-02-27)
Check Item
All bolts are tightened, especially the bolts used for
electrical connection. Flat washers and spring washers are
installed properly.
Cables are bundled neatly, and cable ties are secured evenly
and properly.
Cables are routed for ease of future maintenance and
expansion.
There are no unnecessary adhesive tape or cable ties on the
cables.
Exposed parts near the wiring terminals and lugs are
wrapped in PVC insulation tape or heat shrinking tubing.
The cable routing for power cables and monitoring cables
meets the requirements for routing power cables and signal
cables and complies with the cable routing plan.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Check Before Power-on Commissioning
Result
□Yes □No
□Yes □No
□Yes □No
□Yes □No
□Yes □No
□Yes □No
40

Advertisement

Table of Contents
loading

Table of Contents