6.7.2. Connecting the cables

CAUTION
High voltages in the terminal unit can cause flashover between the
electric potential of different conductors and the electric potential of a
conductor and earth.
When you route and connect the cables, maintain the following
minimum clearances:
70 mm between cable lugs of conductors with a different potential
70 mm between the cable lug of a conductor and the parts with
earth potential
30 mm between cables with a different potential

6.7.2.1. Checking the cable insulation

Measure the insulation of each cable before connection and verify that the
results are within the specification of the cable manufacturer.
Leave the conductors unconnected at both ends until the commissioning
personnel has given permission to connect them.
6.7.2.2. Connecting the cables
Connect the cables to their corresponding busbars:
Transformer cables to the busbars inside the primary PCU (Fig. 6-16)
Motor cables to the busbars inside the COU (Fig. 6-18)
Ground cable to the PE ground busbar
PRODUCT
ACS5000W
Risk of flashover!
DOCUMENT KIND
User manual
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
F
en
102/178