10.6.12. Replacing a fan of an IP54 roof-mounted cooling unit

WARNING
Before starting any work on the fans, de-energize the cooling unit.
The roof-mounted cooling unit as used with IP54 cabinets consists of an air-to-
water heat exchanger and four fans. One fan is redundant and takes over when one
of the other fans fails.
If one fan fails, the red indicator lights up and replacement is required.

10.6.12.1. Replacing a fan

For replacement instructions, see the instruction manual in "Appendix A -
Additional manuals".
1
2

Figure 10-10 Roof-mounted cooling unit (IP54)

1) Control access panel
2) Air-bleed access plate
3) Indicator lights
Dimensions: (L x W x H): 1550 x 975 x 386 mm
Weight: 98 kg
PRODUCT
ACS5000W
Hazardous voltage!
3
4
DOCUMENT KIND
User manual
PREVENTIVE AND CORRECTIVE MAINTENANCE
4) Location of fans (below cover)
5) Lifting eye (one in each corner)
DOCUMENT ID.
3BHS799208 E01
5
REV.
LANG.
PAGE
F
en
177/178