8.10.2. Arc detection with the Arc Guard System™

The Arc Guard System™ detects fast arc faults in the terminal sections of the drive.
When the Arc Guard System detects an arc fault the drive performs protection
firing and immediately opens the main circuit breaker. The Arc Guard monitor and
HMI panel are located in the
COU (Fig. 3-12).
Figure 8-3 Arc Guard™ system with HMI panel
The Arc Guard System™ consists of the following:
Arc Guard unit TVOC-2 with HMI panel
Optical fiber detector
8.10.3. Action after the Arc Guard System™ has been triggered
1. De-energize and ground the drive according to "10.6.2 De-energizing the
drive" on page 165.
2. Search for the location where the arc has been detected.
3. Check the Arc Guard HMI panel messages and use the circuit diagrams.

Figure 8-4 HMI panel

4. Open the power units and localize the defect.
5. Repair the defect or contact support line if needed.
6. Reset the fault on Arc Guard HMI panel.
7. Acknowledge the firing through with parameter 16.26 on the CDP control
panel (only when fault was understood and corrected).
8. Restart the drive.