Energizing The Drive; Stopping The Motor - ABB ACS5000 User Manual

Water-cooled system drives
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

WARNING
Depending on the type of auxiliary supply, the drive can be equipped with
buffer capacitors inside the control unit. During operation, the capacitor
voltage is 300 V (DC).
Wait 5 minutes for the capacitors to discharge.
Before touching a capacitor, verify that the capacitors
are discharged.
NOTICE
and damage when the drive is energized!
Ensure that foreign matter cannot enter the cabinet:
Close the doors and cover openings completely when work is
discontinued.
Retrieve any foreign matter which accidentally dropped into
the cabinet.
10.6.2. De-energizing the drive
The following section describes how to de-energize the drive using the local
operator panel of the drive. If the drive is controlled from remote, follow the
established shutdown procedures.
For instructions on how to use the CDP control panel, see "9 CDP control panel"
on page 133.

10.6.2.1. Stopping the motor

1. Enable the local control mode of the CDP control panel.
2. To stop the motor, press the STOP key.
When the motor has reached zero speed, the display shows ReadyRun.
1 L ->
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
PRODUCT
ACS5000W
Hazardous DC voltage!
Foreign matter and particularly metallic dust can cause failure
DOCUMENT KIND
User manual
PREVENTIVE AND CORRECTIVE MAINTENANCE