ABB ACS560 Quick Installation And Start-Up Manual page 150

General purpose drives standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

150 Diagnostics
Code
Fault / Aux. code
(hex)
aux code visible
only on assist-
ant control panel
and drive com-
poser))
80B5
Signal supervi-
sion 6
9081
External fault 1
9082
External fault 2
9083
External fault 3
EN
9084
External fault 4
HI
9085
External fault 5
A2A1
Current calibra-
tion
FA81
Safe torque off 1
FA82
Safe torque off 2
FF61
ID run
Cause
Fault generated by the sig-
nal supervision function 6.
Fault in external device 1.
Fault in external device 2.
Fault in external device 3.
Fault in external device 4.
Fault in external device 5.
Current offset and gain
measurement calibration
will occur at next start.
Safe torque off function is
active, ie. STO circuit 1 is
broken.
Safe torque off function is
active, ie. STO circuit 2 is
broken.
Motor ID run was not com-
pleted successfully.
What to do
Check the source of the fault (paramet-
er 32.57 Supervision 6 signal).
Check external device and parameter
31.01 External event 1 source.
Check external device and parameter
31.03 External event 2 source.
Check external device and parameter
31.05 External event 3 source.
Check external device and parameter
31.07 External event 4 source.
Check external device and parameter
31.09 External event 5 source.
Informative warning. (See parameter
99.13 ID run requested)
Check safety circuit connections and
parameter 95.04 Control board sup-
ply.
Check
• nominal motor values in parameter
group 98 User motor parameters.
• that no external control system is
connected to the drive.
• that no operation limits prevent the
completion of the ID run. Restore
parameters to default settings and
try again.
• that the motor shaft is not locked.
Cycle the power to the drive (and its
control unit, if powered separately).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents