ABB ACS560 Quick Installation And Start-Up Manual page 134

General purpose drives standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

134 Diagnostics
Code
Warning/Aux
(hex)
code (aux code
visible only on
assistant control
panel and drive
composer)
A8A1
RO life warning
0001 – Relay output 1
0002 – Relay output 2
A8A2
RO toggle warn-
EN
ing
HI
0001 – Relay output 1
0002 – Relay output 2
A8B0
Signal supervi-
sion 1
A8B1
Signal supervi-
sion 2
A8B2
Signal supervi-
sion 3
A8B3
Signal supervi-
sion 4
A8B4
Signal supervi-
sion 5
A8B5
Signal supervi-
sion 6
A8B6
Current limit
warning
Cause
The relay has changed
states more than the recom-
mended number of times.
The relay output is changing
states faster than recom-
mended.
Warning generated by the
signal supervision function
1.
Warning generated by the
signal supervision function
2.
Warning generated by the
signal supervision function
3.
Warning generated by the
signal supervision function
4.
Warning generated by the
signal supervision function
5.
Warning generated by the
signal supervision function
6.
Motor actual current ex-
ceeded the limit defined in
parameter 30.17 Maximum
current.
What to do
Change the control board or stop us-
ing the relay output.
0003 – Relay output 3
Replace the signal connected to the
relay output source with a less fre-
quently changing signal.
0003 – Relay output 3
Check the source of the warning
(parameter 32.07 Supervision 1 sig-
nal).
Check the source of the warning
(parameter 32.17 Supervision 2 sig-
nal).
Check the source of the warning
(parameter 32.27 Supervision 3 sig-
nal).
Check the source of the warning
(parameter 32.37 Supervision 4 sig-
nal).
Check the source of the warning
(parameter 32.47 Supervision 5 sig-
nal).
Check the source of the warning
(parameter 32.57 Supervision 6 sig-
nal).
Reduce the motor load. Check for any
jam or stall in motor.

Hide quick links:

Advertisement

Table of Contents
loading