ABB ACS560 Quick Installation And Start-Up Manual page 144

General purpose drives standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

144 Diagnostics
Code
Fault / Aux. code
(hex)
aux code visible
only on assist-
ant control panel
and drive com-
poser))
8009
800A
EN
64A1
Internal file load
HI
64A4
Rating ID fault
64A6
Adaptive program
64B1
Internal SSW fault
1 - Starting OS time tick failed
2 - Creating system tasks failed
3 - Initializing file system failed
4 - Checking file system failed
64B2
User set fault
64B3
Macro parameter-
ization error
64E1
Kernel overload
6581
Parameter sys-
tem
Cause
The application contains in-
valid tasks.
The application contains an
unknown target (system)
library function.
File read error.
Rating ID load error.
Fault in adaptive program.
A fatal error in the power-up
phase of System Software
(SSW).
Loading user parameter set
failed.
Macro parameterization
failed, eg. Parameter default
value that cannot be
changed has been attemp-
ted to write.
Operating system error.
Note: This fault cannot be
reset.
Parameter load or save
failed.
What to do
In Automation Builder, check applica-
tion task configuration, give a "Clean
all" command, and reload the applica-
tion.
Update the system library or reinstall
Automation Builder.
See the drive-specific log generated
by Automation Builder.
Reboot the control unit. If the problem
persists, contact ABB.
Contact ABB.
Check the fault code extension.
SSW runs in partial functionality
mode.
5 - Initializing WoRm volumes failed
6 - Loading FPGA configuration failed
7 - Loading application program failed
Make sure a valid user parameter set
exists. Reload if uncertain.
Reboot the control unit using paramet-
er 96.08 Control board boot or by
cycling power. If the problem persists,
contact ABB.
Try forcing a save using parameter
96.07 Parameter save manually.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents