PowerCube 5000
User Manual (SmartLi 100Ah)
2.3.3.3 NIM01C3
Panel
Figure 2-16 NIM01C3 panel
(1) SIM card slots (2 PCS)
(4) Run indicator
(7) COM2 port
(10) Handle
Indicators
Table 2-15 Indicator description
Indicator
Color
4G
Green
indicator
Alarm
Red
indicator
Run
Green
indicator
Issue 02 (2020-03-17)
Status
Steady on
Blinking at a period of 2s (on for 0.1s and
then off for 1.9s)
Blinking at a period of 2s (on for 0.1s, off
for 0.1s, on for 0.1s and then off for 1.7s)
Off
Steady on
Off
Copyright © Huawei Technologies Co., Ltd.
(2) 4G indicator
(5) ANT communications port
(8) COM3/CAN port
Description
The dial-up connection is in the data
service state.
The network has been registered.
A network is in search, or no network is
connected.
No alarm is generated.
An alarm is generated.
The NIM01C3 is not running because it
is faulty or has no DC input.
2 Products
(3) Alarm indicator
(6) COM1 port
(9) COM4 port
29