PowerCube 5000
User Manual (SmartLi 100Ah)
This is a class A product. In a living environment, this product may cause radio interference.
Therefore, users may be required to take appropriate measures.
Table C-1 EMC of the ICC cabinet
Item
Electromagnetic
interference (EMI)
Electromagnetic
susceptibility (EMS)
Issue 02 (2020-03-17)
Specifications
Conducted emission (CE)
Radiated emission (RE)
Harmonic current
Voltage fluctuation and
flicker
Electrostatic discharge
(ESD)
Electrical fast transient
(EFT)
Radiated susceptibility (RS)
Conducted susceptibility
(CS)
Surge susceptibility
Lightning protection
Copyright © Huawei Technologies Co., Ltd.
C
CISRP11-2009 Class A
CISRP11-2009 Class A
IEC 61000-3-2
IEC 61000-3-3
IEC61000-4-2, criterion B
Contact discharge: 6 kV; air
discharge: 8 kV
IEC 61000-4-4 (criterion B)
Signal port: 2 kV; AC power port: 2
kV; DC power port: 2 kV
IEC 61000-4-3
10 V/m
IEC 61000-4-6
Power port: 10 V
IEC 61000-4-5 (criterion B)
Dry contact output: 0.5 kV in
differential mode, 1 kV in common
mode
Signal and control ports: 2 kV or
250 A
PV input: 5 kA
System output: level A surge
protection; In: 60 kA; Imax: 100 kA
C EMC
EMC