PowerCube 5000
User Manual (SmartLi 100Ah)
Procedure
Step 1 Turn off the battery cold-start breaker QF2 and BCU power switch QS1 in each lithium
battery cabinet.
Step 2 Wait for 1 minute.
Step 3 Turn on the BCU power switch QS1 in each lithium battery cabinet.
----End
6.3 Logging In to the WebUI
Context
Internet Explorer 11 is used as the example browser.
The system supports Internet Explorer 11.
Procedure
Step 1 Use a network cable to connect the female network cable connector under the monitoring unit
of the ICC cabinet.
Figure 6-1 Connecting a signal cable
Step 2 Open the browser and choose Tools > Internet Options.
Step 3 On the Advanced tab page, ensure that Use TLS 1.0, and Use TLS 1.1 are selected and click
OK.
Issue 02 (2020-03-17)
Copyright © Huawei Technologies Co., Ltd.
6 Operation Guide