Bypass Module (Bps) - Huawei PowerCube 5000 User Manual

Hide thumbs Also See for PowerCube 5000:
Table of Contents

Advertisement

PowerCube 5000
User Manual (SmartLi 100Ah)
Table 2-1 Indicator description
Definition
Power
indicator
Alarm
indicator
Fault
indicator
Table 2-2 Specifications
Parameter
Dimensions (H x W x D)
Weight
Operating temperature
Rated output capacity
AC output voltage
Battery voltage
PV input voltage
PV input power

2.3.2 Bypass Module (BPS)

The BPS supplies power when the power from the DG is in use.
Issue 02 (2020-03-17)
Color
Status
Meaning
Green
Off
The HSU has no input power.
On
The HSU output is normal.
Blinkin
Frequency 0.5 Hz:
g
1. The HSU works in bypass mode (on for 1s and off
2. The HSU has no AC output (on for 0.125s and off
Frequency 4 Hz:
1. The HSU is being configured.
2. The HSU is being loaded online.
Yellow
Off
No protection is triggered by external conditions.
Blinkin
Frequency 0.5 Hz (on for 1s and off for 1s)
g
On
Protection is triggered by external conditions or
temporary malfunction is caused by internal factors.
Red
Off
There is no internal fault or EPO.
On
Protection, protective lockout, EPO, or module
unreadiness is caused by internal component faults.
Description
130 mm x 442 mm x 620 mm
< 34 kg
–25° C to +55° C
33 kVA
380 V AC/400 V AC/415 V AC
336–800 V DC
200–980 V DC
Max.: 33 kW
Copyright © Huawei Technologies Co., Ltd.
for 1s)
for 1.875s)
There is a PFC soft-start failure alarm.
DC bus pre-charging has failed.
2 Products
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartli 100ah

Table of Contents