Huawei PowerCube 5000 User Manual page 109

Hide thumbs Also See for PowerCube 5000:
Table of Contents

Advertisement

PowerCube 5000
User Manual (SmartLi 100Ah)
Item
Network
parameters
Step 2 Set communications parameters for other devices on the MDU of the master cabinet.
Table 5-3 Setting communications parameters
Path
System Info >
Settings >
Communication
Step 3 (For a parallel system) On the MDU of the master cabinet, choose System Info > Settings >
Basic Param, and set Transformer Cabinet SPD Fault Alm. Cond. to Close.
----End
Issue 02 (2020-03-17)
Parameter
Output Volt Adjust
(V)
Altitude (m)
EPO enable
AC Phase Detect
(displayed in a
parallel system)
IP Address
Subnet Mask
Default Gateway
Lihv battery equip IP
Parameter
Monitor Parallel IP (for a
parallel system)
Lihv Battery Equip IP
NetEco Primary IP
NetEcoPort Number
Copyright © Huawei Technologies Co., Ltd.
Setting
EPO (emergency power-off) is performed only
when this parameter is enabled and the EPO switch
is triggered.
When EPO detection is changed from Disable to
Enable, check that the EPO cable is connected
correctly.
Start
If the detection result is abnormal, alarms AC
Input Phase Sequence Incorrect and AC Output
Phase Sequence Incorrect will be generated on the
MDU and WebUI. In this case, reconnect the
cables.
Set this parameter according to the address
information provided by the network administrator.
Set the IP addresses of master and slave cabinets on
the same network segment in the parallel scenario.
The IP address of the lithium battery cabinet must
be the same as the lithium battery cabinet IP
address set for the ICC cabinet.
Setting
IP address of the slave cabinet
IP address of the lithium battery
cabinet
Set this parameter according to the
address information provided by
the network administrator.
Set this parameter as required.
5 Power-on Commissioning
101