4.2

Electrical Connection

Auxiliary Voltage X2

4.2.1
Connect the auxiliary voltage using the terminals X2 on the underside of the device. The assignment of the
terminals is printed on the front of the device, see
not have its own switch, this must be installed externally.
Terminals:
Conductor cross-section (single wire or stranded wire) 1.5 mm
Recommended stripping length
NOTE
i
i
The connection lines must have a minimum length of 50 cm.
[sc_cabel_ferro, 1, --_--]
Figure 4-1
Wrap the connection lines for L and N each 4x and next to one another around the supplied ferrite core.
²
Fix the input and output lines in position using cable ties.
²

Fault-Signaling Connection X7

4.2.2
The terminals X7 are equipped with an isolated contact that is automatically closed by the device in case of an
error.
The assignment of the terminals is printed on the front of the device, see
tions.
Terminals:
Fault-signaling connection
Recommended stripping length
Accessories, Sync Transceiver, Optical/Electrical Converter for Time Synchronization, Manual
C53000-G9050-C168-1, Edition 09.2019
Wrapping the Ferrite Core and Binding the Cables
2.2.1 Arrangement of the
Connections. As the device does
2
to 2.5 mm
2
8 mm to 10 mm (with crimp terminals)
2.2.1 Arrangement of the Connec-
Max. 2.5 mm
2
8 mm to 10 mm (with crimp terminals)

Assembly and Commissioning

4.2 Electrical Connection

39