Device Connections; Arrangement Of The Connections - Siemens 7XV5654-0BA00 Manual

Sync transceiver, optical/electrical converter for time synchronization
Hide thumbs Also See for 7XV5654-0BA00:
Table of Contents

Advertisement

Available languages

Available languages

Device Structure

2.2 Device Connections

2.2
Device Connections

Arrangement of the Connections

2.2.1
[sc_7XV5654_device, 1, --_--]
Figure 2-2
Connections X2, X7, X1
Connection
X2
X7
X1
Optical Fiber Connectors R1 and R2
Connection
R1 and R2
R1 and R2 are the receiving optical fiber connectors of the Sync-Transceiver (refer to
The optical interfaces are set to use positive logic (light idle state: OFF) at the factory. Switched-on light is
treated as active = 1 (high). To adapt to systems that use negative logic, a switch is integrated in each input
channel R1 and R2. If you set the DIP switches 1/2 to ON, you switch to negative logic.
16
Sync Transceiver Front View
Meaning
Auxiliary voltage
Fault-signaling connection M1
2 electrical 24-V outputs on one socket with 9‑pole D-sub connector plug
PE conductor terminal, IEC 60417-5019
Meaning
Optical fiber receiver (ST bayonet closure)
Accessories, Sync Transceiver, Optical/Electrical Converter for Time Synchronization, Manual
Description
DC: L+/AC: L1
DC: L-/AC: N
2, 1
Figure
2-2).
C53000-G9050-C168-1, Edition 09.2019

Advertisement

Chapters

Table of Contents
loading

Table of Contents