Synchronizing Up To 12 Siprotec 4 Or Siprotec 5 Devices - Siemens 7XV5654-0BA00 Manual

Sync transceiver, optical/electrical converter for time synchronization
Hide thumbs Also See for 7XV5654-0BA00:
Table of Contents

Advertisement

Available languages

Available languages

Application Examples

3.3 Synchronizing up to 12 SIPROTEC 4 or SIPROTEC 5 Devices

3.3

Synchronizing up to 12 SIPROTEC 4 or SIPROTEC 5 Devices

This use case is an extension of the basic configuration from chapter
SIPROTEC 5
Devices. The Sync-Transceiver is now operating in channel pairing mode and provides the time
protocol of the GPS receiver to 2 semiconductor switch outputs at the same time. Using the T adaptor cable
7XV5104-3AA00, you can now connect 2 lines from cascaded Y bus cables 7XV5104-0AAxx, each having a
maximum length of 10 m, to the Sync-Transceiver. In this configuration, the number of SIPROTEC 4 or
SIPROTEC 5 devices that can be connected doubles to 2 × 6 = 12.
Table 3-2
Switch
S1/1
S1/2
S1/3
S1/4
[dw_max-12-SIP4-device_with-R1-synch, 1, en_US]
Figure 3-2
26
DIP Switch Positions in the Sync Transceiver
Position
Application-specific (light idle state mode as per the system configuration at the optical-fiber
input R1)
Open
Closed (channel pairing mode)
Open
Synchronizing a Maximum of 12 SIPROTEC 4 Devices Using R1
Accessories, Sync Transceiver, Optical/Electrical Converter for Time Synchronization, Manual
3.2 Synchronizing up to 6 SIPROTEC 4 or
C53000-G9050-C168-1, Edition 09.2019