Synchronizing up to 20 SIPROTEC 3 Devices

In this application example, the hardware configuration is nearly identical to that in chapter
more than 12 SIPROTEC 4 or SIPROTEC 5
can be connected is higher because the SIPROTEC 3 inputs put less of a load on the Sync-Transceiver switching
output. SIPROTEC 3 devices do not have a separate time-synchronization input. Instead, they use the binary
inputs for this. In addition, SIPROTEC 3 devices, in contrast to SIPROTEC 4 or SIPROTEC 5 devices, only process
minute pulses.
NOTE
i
i
Set the switching threshold values of the binary inputs at the SIPROTEC 3 devices to the lowest value
because the drive level is only 24 V due to the Sync-Transceiver.
Table 3-4
Switch
S1/1
S1/2
S1/3
S1/4
Accessories, Sync Transceiver, Optical/Electrical Converter for Time Synchronization, Manual
C53000-G9050-C168-1, Edition 09.2019
Devices. At 20 (2 × 10), only the number of protection devices that
DIP Switch Positions in the Sync-Transceiver
Position
Application-specific (light idle state mode as per the system configuration at the optical-fiber
input R1)
Open
Closed (channel pairing mode)
Open
Application Examples
3.5 Synchronizing up to 20 SIPROTEC 3 Devices
3.4 Synchronizing
29