Synchronizing more than 12 SIPROTEC 4 or SIPROTEC 5 Devices

If you want to synchronize more than 12 SIPROTEC 4 or SIPROTEC 5 devices, you can multiply the optical
output of the GPS receiver by connecting a mini star coupler downstream. Using a mini star coupler and 5
Sync-Transceivers, you can supply up to 60 devices with time telegrams at the same time. By cascading the
mini star couplers and using an appropriate number of Sync-Transceivers, you can continue multiplying the
number of devices to be synchronized.
Table 3-3
Switch
S1/1
S1/2
S1/3
S1/4
Accessories, Sync Transceiver, Optical/Electrical Converter for Time Synchronization, Manual
C53000-G9050-C168-1, Edition 09.2019
DIP Switch Positions in the Sync Transceiver
Position
Application-specific (light idle state mode as per the system configuration at the
optical-fiber input R1)
Open
Closed (channel pairing mode)
Open
3.4 Synchronizing more than 12 SIPROTEC 4 or SIPROTEC 5 Devices