... 7 Installation
External position sensors
A
1
6
B
1
6
1 EDP300 Control Unit
2 Connection cable
3 EDP300 Remote Sensor
4 Actuator
Figure 3: EDP300 with external position sensors
Note
If the device is being operated on a cylinder, for reasons
associated with linearity you should run the Auto Adjust function
for rotary actuators (see chapter Start automatic adjustment on
page 43).
EDP300 control unit with EDP300 remote sensor
A
A
In this version, the components are supplied in two housings,
which together form one harmonized unit.
The following points should be observed during installation:
•
Housing 1 (EDP300 Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
•
Housing 2 (EDP300 Remote Sensor) contains the position
sensor and is mounted on the linear and rotary actuator.
Mechanical mounting is described in chapter Mechanical
mounting on page 17.
•
Electrical connection is carried out as described in
chapter EDP300 Remote Sensor Electrical Connection on
page 25.
2
3
5
4
2
7
5
4
M10931
5 Compressed air supply
6 Set point signal
7 Remote position sensor
Note
To connect the EDP300 Remote Sensor, a cable with the
following specifications needs to be used:
•
3-wire, cross-section 0.5 to 1.0 mm²
•
shielded, with at least 85 % coverage
•
Temperature range up to at least 100 °C (212 °F)
The cable glands must also be approved for a temperature range
up to at least 100 °C (212 °F). The cable glands require a
mounting for the shielding and strain relief for the cable in
addition.
ABB optionally offers a cable gland and cable for the EDP300
Remote Version.
EDP300 Control Unit for remote position sensor
B
In this version the positioner is supplied without a position
sensor.
The following points should be observed during installation:
•
Housing 1 (EDP300 Control Unit) contains the electronics
and pneumatics and is mounted separately from the
actuator.
•
The remote position sensor is mounted on the linear
actuator or rotary actuator. Follow the operating
instructions for the remote position sensor for
mechanical mounting!
•
Electrical connection is carried out as described in
chapter Connection to device - EDP300 Control Unit for
remote position sensor on page 32.