PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
Menu: Switch 2
Menu / parameter
Value range
Input/Output / Digit. Feedback / Switch 2
Switch 2 Funct.
Position Info
Diagnostic State
Switch 2 Value
0 to 100%
Switch 1 Logic
Active High
Active Low
Switch 1 Active
Fall below, Exceeding
Menu: Universal input
Menu / parameter
Value range
Input/Output / Universal input
UI SP Value Max.
4.0 to 20.0 mA
UI SP Value Min.
4.0 to 20.0 mA
UI Damping
0 to 60 s
UI Charact.
Linear, Custom
UI Out Value Min
0.0 to 30000
UI Out Value Max
0.0 to 30000
Description
Use this parameter to select whether the switch is to be used as a limit signal generator or for signaling
diagnostics messages.
Position Info – Evaluate position
Diagnostic State – Assess diagnosis status
Use this parameter to configure the position value as a limit signal generator. It is taken into account
when the 'Switch 2 Funct.' parameter is set to 'Position Info'.
Use this parameter to select the contact logic.
Active High (active) = Output current I > 2.1 mA
Active Low (active) = Output current I < 1.2 mA
Use this parameter to select the edge for activating the switch.
Off – Deactivated
Fall below – If down-scaled
Exceeding – If up-scaled
Description
Use this parameter to specify the upper current range limit for the universal input.
Use this parameter to specify the lower current range limit for the universal input.
Use this parameter to set a damping value for the universal input signal.
Use this parameter to select a function that adjusts the behavior of the positioner to the analog input
signal according to a predefined course. This linearizes the characteristic curves for the valves and
fittings and improves the behavior of the overall control loop.
Linear - linear
Custom - configurable by user
The user-configurable characteristic curve cannot be generated and saved in the device locally, however;
this can only be done via a PC with the appropriate configuration program (DTM / EDD).
Use this parameter to define which value is assigned to the minimum universal input signal 'UI SP Value
Min.'.
Use this parameter to define which value is assigned to the maximum universal input signal 'UI SP Value
Max.'.
67