ABB PositionMaster EDP300 Operating Instruction page 64

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

64
PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D
... 9 Operation
... Parameter descriptions
Menu: Alarm Output
Menu / parameter
Value range
Input/Output / Alarm Output
Alarm Logic
Active High, Active Low
DO Alarm Mask
Alarm Maintenan., Alarm
OoSpec., Alarm Check Fct.,
Alarm Failure
Alarm Simulation
Off, Low, High
Menu: Analog Feedback
Menu / parameter
Value range
Input/Output / Analog Feedback
Analog Out Min.
4.0 to 18.4 mA
Analog Out Max.
5.6 to 20.0 mA
Feedbk. Charact.
Direct, Reverse
AO Alarm Mask
Alarm Maintenan.
Alarm OoSpec.
Alarm Check Fct.
Alarm Failure
AO Simulation
Off
Low
High
Input current
HW Alarm Current
Description
Use this parameter to define the contact logic for the alarm output.
Active High –> I > 2.1 mA
Active Low –> I < 1.2 mA
Use this parameter to select which general alarms are output as an alarm current, depending on the
activated Namur classification group.
Alarm Maintenan. – Maintenance needed
Alarm OoSpec. – Operation outside specifications
Alarm Check Fct. – Functional test needed
Alarm Failure – Errors
The presence of an alarm can be simulated here in order to output the alarm current.
Description
Use this parameter to specify the lower current range limit for the analog feedback. The current range
corresponds to the configured stroke range.
Note
The current range limits can be freely configured between 4 and 18.5 mA. However, the current range
must not be smaller than 10 % (1.6 mA).
Use this parameter to specify the upper current range limit for the analog feedback. The current range
corresponds to the configured stroke range.
Note
The current range limits can be freely configured between 4 and 20 mA. However, the current range
must not be smaller than 10 % (1.6 mA).
Use this parameter to specify the characteristic curve for the analog feedback.
Direct (rising) = Position 0 to 100 % = Signal 4 to 20 mA
Reverse (falling) = Position 0 to 100 % = Signal 20 to 4 mA
When a general alarm is issued, an alarm current can be sent via the analog position feedback. These
alarm groups are defined in accordance with Namur NE107. A high alarm current ( 'High' i >21 mA), low
alarm current ('Low' I < 3.6 mA, or 'Off' can be set for each individual group.
The analog position feedback function is simulated in this parameter group.
Off – Terminate simulation.
Reverse – Alarm current I < 3.6 mA
High – Alarm current I > 21 mA
Input current – The input current of the positioner is output.
HW Alarm Current – The 'AO Alarm Current' set in 'Service Mode' is output.