ABB PositionMaster EDP300 Operating	 Instruction

ABB PositionMaster EDP300 Operating Instruction

Digital positioner
Hide thumbs Also See for PositionMaster EDP300:
Table of Contents

Advertisement

A B B M E A S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N
PositionMaster EDP300
Digital Positioner
Introduction
EDP300
The PositionMaster EDP300 has an integral mount
design, features a modular structure and offers an
outstanding price-performance ratio. Fully
automatic determination of the control parameters
and adaptation to the positioner allow for
considerable time savings as well as optimum
control behavior. Due to its characteristics, the
positioner is suited for even the most demanding
operating conditions.
Digital Positioner for the
positioning of pneumatically
controlled final control elements.
Additional Information
Additional documentation on PositionMaster
EDP300 is available for download free of charge at
www.abb.com/positioners.
Alternatively simply scan this code:

Advertisement

Table of Contents
loading

Summary of Contents for ABB PositionMaster EDP300

  • Page 1 Introduction Additional Information — EDP300 The PositionMaster EDP300 has an integral mount Additional documentation on PositionMaster design, features a modular structure and offers an EDP300 is available for download free of charge at outstanding price-performance ratio. Fully www.abb.com/positioners.
  • Page 2: Table Of Contents

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Table of contents Change from one to two columns Safety ................4 Transport and storage ..........15 Inspection ................15 General information and instructions ........4 Transporting the device ............15 Warnings ..................4 Storing the device ..............
  • Page 3 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 15 Additional documents ..........80 Commissioning ............37 Safety instructions ..............37 16 Accessories .............. 80 Checks prior to commissioning .......... 37 Extension modules ..............80 Mechanical mounting checks ..........37 Accessories ................80 Operation ..............
  • Page 4: Safety

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 1 Safety Warnings General information and instructions These instructions are an important part of the product and The warnings in these instructions are structured as follows: must be retained for future reference.
  • Page 5: Intended Use

    / or theft of data or information. ABB Automation Products GmbH and its affiliates are not liable for damages and / or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and / or theft of data or information.
  • Page 6: Use In Potentially Explosive Atmospheres

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Mounting Note The installation, commissioning, maintenance and repair of Further information on the Ex-Approval of devices can be found devices in potentially explosive atmospheres must only be in the type examination certificates or the relevant certificates carried out by appropriately trained personnel.
  • Page 7: Operation With Flammable Gases

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D ATEX and IECEx temperature data Operation with flammable gases Type of protection Ex i, intrinsic safety Observe the following points when operating a device with flammable gases: Temperature Ambient temperature Surface temperature •...
  • Page 8: Atex Und Iecex Electrical Data

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx ATEX und IECEx electrical data Type of protection Ex i, intrinsic safety Basic device Signal circuit (AI) Module for analog feedback (AO)
  • Page 9: Type Of Protection Ex N - Non-Sparking

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Type of protection Ex n - non-sparking Basic device Signal circuit (AI) Terminals +11 / 12 Electrical values 22 mA; U 30 V Digital input (DI) Terminals +81 / 82 Electrical values...
  • Page 10: Use In Potentially Explosive Atmospheres

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 3 Use in potentially explosive atmospheres in accordance with FM and CSA Change from one to two columns Mounting Note The installation, commissioning, maintenance and repair of Further information on the Ex-Approval of devices can be found...
  • Page 11: Operation With Flammable Gases

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Temperature data Operation with flammable gases Note Observe the following points when operating a device with Legibility of the display is guaranteed at an ambient flammable gases: temperature of 20 to 70 °C. At 20 °C and lower, legibility can •...
  • Page 12: Electrical Data

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 3 Use in potentially explosive atmospheres in accordance with FM and CSA Electrical data Basic device Signal circuit (AI) Module for analog feedback (AO) Terminals +11 / 12 Terminals +31 / 32 Temperature class T1 –...
  • Page 13: Design And Function

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 4 Design and function Schematic diagram Basic device Optional upgrades M M 10112-01 A Electronics 7 Analog feedback B Pneumatics 8 Digital feedback C Position sensor 9 Emergency shutdown module 1 4 to 20 mA / Bus connection...
  • Page 14: Principle Of Operation

    … 4 Design and function Principle of operation The PositionMaster EDP300 is an electronically configurable positioner with communication capabilities designed for mounting on pneumatic linear or rotary actuators. Fully automatic determination of the control parameters and adaptation to the positioner allow for considerable time savings as well as optimum control behavior.
  • Page 15: Transport And Storage

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 6 Transport and storage 7 Installation Inspection Safety instructions Check the devices immediately after unpacking for possible CAUTION damage that may have occurred from improper transport. Risk of injury due to incorrect parameter values!
  • Page 16: External Position Sensors

    100 °C (212 °F). The cable glands require a mounting for the shielding and strain relief for the cable in addition. ABB optionally offers a cable gland and cable for the EDP300 Remote Version. EDP300 Control Unit for remote position sensor...
  • Page 17: Mechanical Mounting

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Mechanical mounting General Operating range for linear actuators: The operating range for linear actuators is ±45° symmetrically to the longitudinal axis. The usable span within the operating range is at least 25° (recommended figure 40°). The usable span does not necessarily need to run symmetrically to the longitudinal axis.
  • Page 18: Mounting On Linear Actuators

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Mechanical mounting Mounting on linear actuators For mounting on a linear actuator in accordance with DIN / IEC 534 (lateral mounting as per NAMUR), the following attachment kit is available:...
  • Page 19 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 4. Hold the prepared positioner (with the mount bracket still loose) on the actuator so that the follower pin for the lever enters the follower guide to determine which tap holes on the positioner must be used for the mount bracket.
  • Page 20 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Mechanical mounting Position of actuator bolt The actuator bolt for moving the potentiometer lever can be mounted permanently on the lever itself or on the valve stem. Depending on the mounting method, when the valve moves the...
  • Page 21: Mounting On Control Valves

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Mounting on control valves Mounting on rotary actuator For mounting on part-turn actuators in accordance with VDI / VDE 3845, the following attachment kit is available: M10128-01 1 Washers 3 O-ring 2 Screws...
  • Page 22 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Mechanical mounting M10421-01 1 Attachment bracket M10424-01 Figure 18: Screwing the attachment bracket onto the positioner Figure 17: Mounting the adapter on the positioner 1. Determine the mounting position (parallel to actuator or at 90°...
  • Page 23: Electrical Connections

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Electrical connections Safety instructions DANGER Risk of explosion for devices with local communication interface (LCI) A local communication interface (LCI) may not be operated in hazardous areas. • Never use the local communication interface (LCI) on the...
  • Page 24: Positioner / Edp300 Control Unit Electrical Connection

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Electrical connections Positioner / EDP300 Control Unit Electrical Connection D Limit 1 Limit 2 51 52 53 41 42 43 Limit 1 Limit 2 +11 -12 +81 -82 +83 -84...
  • Page 25: Edp300 Remote Sensor Electrical Connection

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D EDP300 Remote Sensor Electrical Connection Limit 1 Limit 2 Limit 1Limit 2 +51 -52 +41 -42 51 52 53 41 42 43 M10949 M10949 A Basic device 1 Position sensor B Options...
  • Page 26: Module For Analog Feedback Ao

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Electrical connections Option modules Set point signal analog (two-wire technology) Module for analog feedback AO* Terminals +11 / 12 Without any signal from the positioner (e.g. ‘no power’ or ‘initializing’) the module sets the output to >...
  • Page 27: Module For The Emergency Shutdown Function

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Module for the emergency shutdown function* Limit switch When the 24 V DC signal is interrupted, the I/P module executes The limit switch can either be equipped with proximity switches the respective safety function, depending on the mechanical or with potential-free microswitches.
  • Page 28: Connection On The Device

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Electrical connections Connection on the device M 20 mm / 1/2" M10950 1 Blind plug 4 Terminals attachment set for digital feedback 2 Cable gland 5 Terminals basic device...
  • Page 29 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Option modules Cross section Rigid / flexible wires 0.14 to 1.5 mm (AWG26 to AWG17) Flexible with wire end sleeve no 0.25 to 1.5 mm (AWG23 to AWG17) plastic sleeve Flexible with wire end sleeve 0.25 to 1.5 mm...
  • Page 30: Connection To Device - Edp300 Control Unit With Edp300 Remote Sensor

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Electrical connections Connection to device - EDP300 Control Unit with EDP300 Remote Sensor Housing 1 (EDP300 Control Unit) Housing 2 (EDP300 Remote Sensor) M 20 mm / M 20 mm / NPT 1/2"...
  • Page 31 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Electrical connection Connect the positioner (EDP300 Control Unit, housing 1) and remote position sensor (EDP300 Remote Sensor, housing 2), while following the instructions below: • The EDP300 Remote Sensor and the EDP300 Control Unit are adjusted to each other.
  • Page 32: Remote Position Sensor

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Electrical connections Connection to device - EDP300 Control Unit for remote position sensor M 20 mm / M 20 mm / 1/2" 1/2" M10834-01 1 Terminals for remote position sensor...
  • Page 33: Installing The Option Modules

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Installing the option modules Electrical connection Note Connect the positioner (EDP300 Control Unit) and remote The supply voltage must be switched off before the option position sensor while observing the following instructions: modules are installed.
  • Page 34: Installing The Mechanical Position Feedback

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation … Installing the option modules Installing the mechanical position feedback 1. Loosen the screws for the housing cover and remove it. 1. Loosen the screws for the housing cover and remove it.
  • Page 35: Setting The Mechanical Limit Switch With Proximity Switches

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Setting the mechanical limit switch with proximity Setting the mechanical limit switch with 24 V switches microswitches 1. Loosen the screws for the housing cover and remove it. 2. Select the ‘Manual Adjustment’ operating mode and move the final control element by hand into the desired switching position for contact 1.
  • Page 36: Pneumatic Connections

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 7 Installation Pneumatic connections Connection on the device Note The positioner must only be supplied with instrument air that is free of oil, water, and dust (in gas configuration with dried natural gas).
  • Page 37: Air Supply

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 8 Commissioning Safety instructions Air supply Note The electrical power supply and supply air pressure data indicated on the name plate must be complied with during Instrument air commissioning. Purity Maximum particle size: 5 m...
  • Page 38 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 8 Commissioning … Mechanical mounting checks Moving to end positions after completion of automatic Moving to end positions with a new device adjustment Process display Process display 1. Use to move to the relevant end positions.
  • Page 39: Operation

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 9 Operation Safety instructions Menu navigation CAUTION Risk of injury due to incorrect parameter values! Incorrect parameter values can cause the valve to move unexpectedly. This can lead to process failures and result in injuries.
  • Page 40: Menu Levels

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation Menu levels There are three menu levels below the process display. Process display Information level Operating mode Diagnosis Auto Adjust Operator Page 1 Adaptive Signals View Control Manual SP...
  • Page 41: Process Display

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Process display Switching to the information level (Operator Menu) On the information level, the operator menu can be used to display diagnostic information and choose which operator 50.0 pages to display. Position °%...
  • Page 42: Switching The Operating Mode

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation Switching the operating mode The operating mode is displayed and changed in the operating Description of operating modes modes menu. Additionally, it is possible to switch to the configuration level...
  • Page 43: Start Automatic Adjustment

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Start automatic adjustment Symbol Operating mode The Auto Adjust function of the device can be configured and Manual set point, fixed control started in the ‘Operating mode’ menu. The valve is adjusted manually within the stroke range using the direction buttons.
  • Page 44: Switching To The Configuration Level (Parameterization)

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Switching the operating mode Switching to the configuration level (parameterization) Note The ‘Autoadjust Mode’ can be preset at the configuration level in The device parameters can be displayed and changed on the ‘...
  • Page 45: Error Messages On The Lcd Display

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Error messages on the LCD display Numerical entry When a numerical entry is made, a value is set by entering the In the event of an error, a message consisting of a symbol and individual decimal positions.
  • Page 46: Overview Of Parameters On The Configuration Level

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation Overview of parameters on the configuration level Note This overview of parameters shows all the menus and parameters available on the device. Depending on the version and configuration of the device, not all of the menus and parameters may be visible in it.
  • Page 47 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Input/Output Digital Input DI Function DI Default SP DI Logic Alarm Output Alarm Logic DO Alarm Mask Alarm Simulation Alarm Maintenan. Alarm OoSpec. Alarm Check Fct. Alarm Failure Analog Feedback Analog Out Min.
  • Page 48 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Overview of parameters on the configuration level SW 2 Mask Map Alarm Maintenan. Alarm OoSpec. Alarm Check Fct. Alarm Failure Universal input UI SP Value Max. UI SP Value Min.
  • Page 49 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Device Info Hardware Rev. Software Rev. Mounting Date Commun. Tag Device Address Descriptor Device Message Pneumatic Type Stroke Time Up Stroke Time Dn Service Service Mode Factory Setting Adjust Sensors Adjust All...
  • Page 50: Parameter Descriptions

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation Parameter descriptions Menu Easy Setup Menu / parameter Value range Description Easy Setup Language English, Deutsch, Français, Selects the menu language Italiano, Español, Português Actuator Type Linear, Rotary Use this parameter to configure the positioner for operation on a linear actuator (sensor range ±30°) or on a rotary actuator (sensor range ±45°).
  • Page 51 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu / parameter Value range Description Easy Setup (continued) Autoadjust Mode Full, Controller, Valve Range, Use this parameter to define the mode or scope of the Auto Adjust function. Zero, Locked •...
  • Page 52: Menu Device Setup

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu Device Setup Menu / parameter Value range Description Device Setup Actuator Type Linear, Rotary Use this parameter to configure the configuration-, parameterization instruction for the positioner for operation on a linear actuator (sensor range ±30°) or on a rotary actuator (sensor range ±45°).
  • Page 53 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Setpoint Menu / parameter Value range Description Device Setup / Setpoint SP Range Min. 4.0 to 18.4 mA The setpoint range is the range of the input current as a percentage of the operating range of the fittings from 0 to 100 %.
  • Page 54 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu / parameter Value range Description Device Setup / Setpoint (continued) SP Charact. Curve Linear Use this parameter to select a function that adjusts the behavior of the positioner to the analog input signal in accordance with a predefined course.
  • Page 55 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu: Range Settings Menu / parameter Value range Description Device Setup / Range Settings Valve Rng Calib. Upper Valve Rng 0.0 to 100.0 % Normally, the valve range is determined automatically during Auto Adjust. A partial run of Auto Adjust that is limited to the control parameters or valves and fittings without end stops, however, requires manual adjustment of the valve range.
  • Page 56 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu / parameter Value range Description Device Setup / Range Settings (continued) Upper Working Rng 0.0 to 100.0 % The working range can be configured to be smaller than the maximum mechanical working range. The set point range always refers to the configured working range.
  • Page 57 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D End Stop Behav. Menu / parameter Value range Description Device Setup / End Stop Behav. Tight Shut 0% 0 to 45.0 The shut-off value is a percentage of the working range from which the 0 % position is approached.
  • Page 58: Menu: Display

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu: Display Menu / parameter Value range Description Display Language English, Deutsch, Français, Selects the menu language Italiano, Español, Português Engineering Units Temperature Use this parameter to select the units to be displayed.
  • Page 59: Menu: Controller

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu: Controller Menu / parameter Value range Description Controller Zone 1 to 100 in steps of 1 This parameter specifies the point at which the control structure is switched over when the dead band is being approached.
  • Page 60 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu / parameter Value range Description Controller (continued) KP Up 1.0 to 400.0 Use this parameter to adjust the KP value for the up positioning direction (towards 100 %).
  • Page 61 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu / parameter Value range Description Controller (continued) Y-Offset Up 1 to 100.0 % Use this parameter to adjust the Y offset for the up positioning direction (towards 100 %). The ‘offset for the set point signal’ linearizes the behavior of the I/P module used and enables rapid compensation even in the case of small control deviations.
  • Page 62: Menu: Input/Output

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu: Input/Output Menu / parameter Value range Description Input/Output Digital Input DI Function Selection of functions or states that are executed or adopted if the ‘digital input’ has been activated.
  • Page 63 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu: Digital Input Menu / parameter Value range Description Input/Output / Digital Input DI Function • Off – No function Hold Last SP • Hold Last SP – Last set point is retained Hold User SP •...
  • Page 64 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu: Alarm Output Menu / parameter Value range Description Input/Output / Alarm Output Alarm Logic Active High, Active Low Use this parameter to define the contact logic for the alarm output.
  • Page 65 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu: Digital Feedback Menu / parameter Value range Description Input/Output / Digital Feedback Switch 1 Switch 1 Funct. The function of switch 1 is configured in this parameter group. Switch 1 Value •...
  • Page 66 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu: SW 1 Mask Map Menu / parameter Value range Description Input/Output / Digital Feedback / SW 1 Mask Map Alarm Maintenan. On, Off When a general alarm is issued, an alarm current can be sent via the analog position feedback. These alarm groups are defined in accordance with Namur NE107.
  • Page 67 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu: Switch 2 Menu / parameter Value range Description Input/Output / Digit. Feedback / Switch 2 Switch 2 Funct. Position Info Use this parameter to select whether the switch is to be used as a limit signal generator or for signaling diagnostics messages.
  • Page 68: Menu: Communication

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu: Communication Menu / parameter Value range Description Communication HART Version HART 5, HART 7 Use this parameter to define the HART protocol via which the device is to communicate.
  • Page 69: Menu: Diagnosis

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu: Diagnosis Menu / parameter Value range Description Diagnosis Partial Stroke PS Configuration, PS ‘Partial Stroke Test’ is used to test the mobility of the safety-related valves and fittings. For this Interval, PS Start Now purpose, the valve is moved by a configurable amount in the direction of the safety position (venting of positioner output 1).
  • Page 70 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu: Partial Stroke Menu / parameter Value range Description Diagnosis / Partial Stroke PS Configuration PS Vent Amount, • PS Vent Amount: Position change in the direction of the safety position (venting of positioner output 1) by which the valve is to be moved.
  • Page 71: Menu: Device Info

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu: Device Info Note This menu is only used to display the device parameters. The parameters are displayed independently of the configured access level, but cannot be changed. Menu / parameter Value range...
  • Page 72: Menu: Service

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 9 Operation … Parameter descriptions Menu: Service Menu / parameter Value range Description Service Off, On * Service Mode Activate service mode. CAUTION Danger of crushing! If Service Mode is set to ‘On’, the valve moves to its pneumatic safety position. In the case of the ‘venting’...
  • Page 73 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Menu / parameter Value range Description Service (continued) Remote Sensor* Off, On If an external position sensor is connected, this parameter must be set to ‘On’. Sensor Type * Standard Use this parameter to select the version of the installed position sensor.
  • Page 74: Diagnosis / Error Messages

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 10 Diagnosis / error messages Calling up the error description Additional details about the error that has occurred can be called up on the information level. Process display Electronics 1. Use to switch to the information level (Operator Menu).
  • Page 75: Possible Error Messages

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Possible error messages Priority Fault message Possible cause Troubleshooting the Instrument Group Position measurement Defective position sensor Replace position sensor Sensor Failure * Valve blocked Friction too high Valve requires maintenance Actuator...
  • Page 76 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 10 Diagnosis / error messages … Possible error messages Priority Fault message Possible cause Troubleshooting the Instrument Group Leakage in actuator Leakage inside the actuator Check the actuator diaphragms Actuator Pressure NV Data defect...
  • Page 77 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D Priority Fault message Possible cause Troubleshooting the Instrument Group Binary input active Digital input activated by the Deactivate the digital input Special user Requirements Switchpoint 1 exceeded Valve has passed limit 1 position Depends on application...
  • Page 78: Maintenance

    All devices delivered to ABB must be free from any hazardous materials (acids, alkalis, solvents, etc.). Please contact Customer Center Service acc. to page 5 for...
  • Page 79: Supplemental Specifications

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 14 Supplemental specifications Transmission data and contributing Actuator travel factors Rotation angle Output Y1 Used range 25 … 270° for rotary actuator Increasing set point signal 0 to 100 % 25 … 60° for linear actuator...
  • Page 80: Ambient Conditions

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 14 Supplemental specifications 16 Accessories Ambient conditions Extension modules Mechanical position indicator Ambient temperature range Indicator disk in housing cover linked with device feedback During operation, storage, 40 to 85 °C ( 40 to 185 °F) shaft.
  • Page 81: Appendix

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D 17 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
  • Page 82: Control Drawing 901305

    PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 17 Appendix Control Drawing 901305...
  • Page 83 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D...
  • Page 84 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 17 Appendix … Control Drawing 901305...
  • Page 85 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D...
  • Page 86 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D … 17 Appendix … Control Drawing 901305...
  • Page 87 PositionMaster EDP300 DIGITAL POSITIONER | OI/EDP300-EN REV. D...
  • Page 88 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.